Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM00373
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00373 3/25/08 1. Registrant shall date seal and provide Expiration Date. 2. Clarify purpose of junction boxes on Revision 2. 3. Specify location of relocated panel on Revision 2. If it is the same as Panel 135 on the demo plan, clarify this. |