Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM00373
Parcel: 10309006F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00373
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2008 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Approved
02/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved If the service to the building is monitored by Runway Drive
Industrial Center L.L.C., this would provide a very loose qualification for compliance with NEC 240.24 (B) Exception #1. However, I would be willing to consider it for the service disconnecting means and any fusing/circuit breakers at that level of the system.

If as I understand it a panel and disconnect which feed Suite 151 are in an area of limited access, this is not valid unless Building Superintendent personnel are continuously available on site. And since this is to be independently metered, it is hard to visualize where the meter will be installed for Suite 155.

Now, this email and reply are theoretical because the plans do not lay any of this out.
02/21/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved February 21, 2008
FLOODPLAIN USE PERMIT # T08OT00435
PROJECT ADDRESS: 4001 N Runway Drive
APPLICANT'S NAME: Acorn Associates Architecture
PROPERTY OWNER: Runway Industrial


This parcel lies in a FEMA AO (Depth 1') Zone map number 040076 C 1619K, effective date February 8, 1999. Federal law requires that a flood insurance policy be obtained as a condition of a federally backed mortgage or loan that is secured by a building located within a SFHA. The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as:

4001 N Runway Drive, Tucson, AZ 85718, FREEWAY INDUSTRIAL PTN LOTS 39 40 41 48 49 50 LYG SW & ADJ RUNWAY DR. In a portion of Township 13 South, Range 13 East, Section 28, TI - Warehouse.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following conditions apply to this permit:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

2) This parcel a lies entirely within a FEMA AO (Depth 1') Zone, 100-year floodplain. Therefore, the proposed development is subject to substantial improvement requirements.

Substantial Improvement means any reconstruction, repair, rehabilitation, addition or other improvements of a structure, the cost of which equals or exceeds fifty (50) percent of the market value of the structure before the "start of construction" of the improvements. This term includes structures, which have incurred "substantial damage" regardless of the actual repair work performed.

Per Sec. 26-4.1 Nonconforming development.

(a) Improvements to, or Reconstruction of, Existing Nonconforming Development:

(1) Any structure which is substantially improved at a cost equal to or exceeding fifty (50) percent of the full cash value of the structure as shown on that latest assessment rolls of the county assessor wither (a) before the improvement or repair is started, or (b) if the structure has been damaged and is being restored, before the damage occurred, shall conform to these regulations. At the time of improvement or reconstructing the structure or development, floodproofing (non-residential structures only) may be considered as one of the means if bringing it in compliance with this chapter.

The proposed improvement is considered a substantial improvement since the building is located within a FEMA SFHA and does not a have an elevation certificate on file. The cost of the improvements is estimated at $48,058.00, per estimate provided by John E. Hoffman, Better Built Builders Inc., for labor and material. The current assessed value of the structure is $714,138.00.


The assessed value of the structure, calculated to be $714,138.00 per Pima County Assessor Detailed Valuation Report Construction Cost Model (Dated Feb-21-2008). Any cumulative improvements would need to be under a total 50% substantial improvement amount of $357,069.00. The current proposed improvement is 6% of the structure value, so any further improvements would result in other floodplain use permit review, flood proofing design, and/or other substantial improvement requirements.

3) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T08OT000435 FOR INFORMATION PLEASE CALL 791-5550."

4) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.

5) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

6) See the associated activity T08CM00373.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Development Services Department, Engineering Division.

(EXPIRATION DATE) Month: 2 Day: 21 Year: 2009

CONTRACTOR: Acorn Associates Architecture
ADDRESS: 4400 E Broadway Blvd, Suite #505, Tucson, AZ 85711
PHONE: (520) 881-0731
OWNER: Runway Industrial Center LLC
ADDRESS: PO Box 31642, Tucson, AZ 85718
PHONE: (520) 975-5131


__________________
SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
02/25/2008 GERRY KOZIOL WWM REVIEW Approved
02/25/2008 HEATHER THRALL ZONING REVIEW Approved
02/25/2008 DAVE MANN FIRE REVIEW Approved