Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM00355
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00355
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00355 2/7/08

1. Put electrical load on Panel Schedule for Ckt 2P-7.
2. Existing service electrical load is given at 208V, but the service itself is at 480V. Please clarify.
3. Configuration violates NEC 240.21 (C) for transformer secondary conductors.
02/08/2008 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/08/2008 GBONILL1 WWM REVIEW Needs Review
02/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/08/2008 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review