Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00355
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00355 2/7/08 1. Put electrical load on Panel Schedule for Ckt 2P-7. 2. Existing service electrical load is given at 208V, but the service itself is at 480V. Please clarify. 3. Configuration violates NEC 240.21 (C) for transformer secondary conductors. |
02/08/2008 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
02/08/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
02/08/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
02/08/2008 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |