Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00354
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00354
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00354 2/7/08

1. Put electrical load on Panel Schedule for Ckt P-7.
2. Existing service electrical load is given at 208V, but the service itself is at 480V. Please clarify.
02/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/08/2008 GBONILL1 WWM REVIEW Needs Review
02/08/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2008 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/08/2008 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review