Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00354
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00354 2/7/08 1. Put electrical load on Panel Schedule for Ckt P-7. 2. Existing service electrical load is given at 208V, but the service itself is at 480V. Please clarify. |
02/08/2008 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
02/08/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/08/2008 | GBONILL1 | WWM | REVIEW | Needs Review | |
02/08/2008 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |