Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM00339
Parcel: 116021720

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM00339
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2008 GERRY KOZIOL WWM REVIEW Approved
03/03/2008 HENRY DURAZO BUILDING-RESIDENTIAL REVIEW Denied 1) FLOOR AND ELECTRICAL PLAN REQUIRED OF ADJOINING ROOMS, INCLUDING EXISTING LIVING ROOM AND KITCHEN CONVERTED TO PORTION OF LIVING ROOM
2) SPECIFY TYPE OF WINDOW AND U-VALUE
3) PLUMBING WASTE, SHOW SIZE OF LINE TO EACH FIXTURE
4) SHOW WHERE WATER LINE IS COMING FROM, NOTE: 3/4" MINIMUM REQUIRED. TWO FIXTURE MAXIMUM ON 1/2" LINE
5) PRESSURE TEMPERATURE RELIEF LINE REQUIRED AT WATER HEATER TO OUTSIDE
6) SUBMIT ELECTRICAL CALCS FOR EXISTING DEMAND ON 200 AMP SERVICE
7) SUBMIT SPECS ON PROPOSED WATER HEATER CONFIRMING 20 AMP MAXIMUM REQUIREMENT
8) OUTLETS MISSING AT BAY WINDOW. OUTLETS SHALL BE 6' FROM OPENINGS AND NOT OVER 12' APART
9) ALL KITCHEN OUTLETS SHALL BE ON 20 AMP CIRCUIT
10) CIRCUIT 14-16 IS A TWO POLE 30 AMP, FOR WHAT PURPOSE AND WHERE ?
11) SIZE OF WALL HEATER IN BATHROOM
12) EXTERIOR LIGHT FIXTURE BY WEST KITCHEN EXIT SHALL BE SHIELDED

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2008 CPIERCE1 OUT TO CUSTOMER Completed
03/10/2008 SHANAE POWELL REJECT SHELF Completed