Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM00339
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/05/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/03/2008 | HENRY DURAZO | BUILDING-RESIDENTIAL | REVIEW | Denied | 1) FLOOR AND ELECTRICAL PLAN REQUIRED OF ADJOINING ROOMS, INCLUDING EXISTING LIVING ROOM AND KITCHEN CONVERTED TO PORTION OF LIVING ROOM 2) SPECIFY TYPE OF WINDOW AND U-VALUE 3) PLUMBING WASTE, SHOW SIZE OF LINE TO EACH FIXTURE 4) SHOW WHERE WATER LINE IS COMING FROM, NOTE: 3/4" MINIMUM REQUIRED. TWO FIXTURE MAXIMUM ON 1/2" LINE 5) PRESSURE TEMPERATURE RELIEF LINE REQUIRED AT WATER HEATER TO OUTSIDE 6) SUBMIT ELECTRICAL CALCS FOR EXISTING DEMAND ON 200 AMP SERVICE 7) SUBMIT SPECS ON PROPOSED WATER HEATER CONFIRMING 20 AMP MAXIMUM REQUIREMENT 8) OUTLETS MISSING AT BAY WINDOW. OUTLETS SHALL BE 6' FROM OPENINGS AND NOT OVER 12' APART 9) ALL KITCHEN OUTLETS SHALL BE ON 20 AMP CIRCUIT 10) CIRCUIT 14-16 IS A TWO POLE 30 AMP, FOR WHAT PURPOSE AND WHERE ? 11) SIZE OF WALL HEATER IN BATHROOM 12) EXTERIOR LIGHT FIXTURE BY WEST KITCHEN EXIT SHALL BE SHIELDED |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/10/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
03/10/2008 | SHANAE POWELL | REJECT SHELF | Completed |