Permit Number: T08CM00323
Parcel: 12006316A

Address:
4207 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM00323
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2008 TERRY STEVENS ZONING REVIEW Approved
04/14/2008 TERRY STEVENS ZONING HC SITE REVIEW Approved
04/14/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. The requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B

2. Landscape must be installed per the previously approved landscape plans.

3. A street landscape border per LUC 3.7.2.4, is an area running the full length of the street property line bounding the site except for points of ingress-egress. Landscape borders are required along all street frontages per approved plan.

4. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4. Provide equal amount of plants indicated on the approved plan for street frontages

5. Canopy trees must be provided for street landscape borders per LUC 3.7.2.4. Two trees are required for buffer along Columbia St.

6. A 30" continuous screen along Columbia St. for vehicle use area must be provided per LUC Table 3.7.2-I. Show the location and materials for all screening elements.

7. Whether or not required by this Division, screens along a street frontage must be located on the development side of the street landscape border so that they do not obstruct the view of the street landscape border from the street.

8. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

9. Additional comments may apply.
05/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: May 30 2008
SUBJECT: Site Plan
TO: Ruperto Cervantes/ Francisco Contreras
LOCATION: 4207 S 6th Avenue, T14S, R13E, Section 36, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM00323 (Second Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan.

Site Plan:

1. See comments from Ron Brown.
2. See Comments from Ron Brown.
3. Complied
4. DS Sec.2-02.2.1.A.10: Provide future site visibility triangles (SVTs), labeled and dimensioned. Refer to DS Sec.3-01.5.3 for line of site matrix for SVT. Show SVTs from Columbia along 6th Ave.
5. Complied
6. Indicate curb returns for MS&R and call out radius on plans. Responce acknowledged. Provide letter from Transportation if curb returns are not required - please note only Transportation can waive requirement.
7. Complied
8. Complied
9. Complied
10. Complied
11. Waived - not full compliance.
12. Label existing and future dimensioned right-of-way, as exising/future per D.S. 2-02.2.1.19.
13. Complied
14. Complied
15. Complied
16. Label dimensions from street monument lines to existing to existing curbs, sidewalks, driveways and utility lines per D.S. 2-02.2.1.21.
17. Complied
18. Complied
19. Complied
20. Waived - existing trash enclosure and not full code compliance.
21. Waived - Not full code compliance
22. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
23. Complied
24. Complied
25. Complied
26. Complied
27. Complied
28. On landscaping plan along north property line, please adjust text so that it is not overlapping and is easier to read.
29. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2008 THAUSER1 OUT TO CUSTOMER Completed
06/06/2008 GERARDO BONILLA REJECT SHELF Completed