Permit Number: T08CM00323
Parcel: 12006316A

Address:
4207 S 6TH AV

Review Status: Completed

Review Details: SITE

Permit Number - T08CM00323
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2008 DAVE MANN FIRE REVIEW Approved
02/04/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. The requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B

2. Submit a landscape plan to verify the site meets minimum requirements. Landscape must be installed per the previously approved landscape plans.

3. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I. Show the location and plant material for screening element.

4. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

5. Additional comments may apply.
02/05/2008 ANDREW CONNOR NPPO REVIEW Approved
02/06/2008 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM00323
4207 S. 6th Ave.
Site Plan

TRANSMITTAL DATE: 02/05/08

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per the DNR violation case number T07DV12462 and the last approved site plan provided the 5' wall indicated as existing has not been permitted. Indicate on the plans the wall as being a new 5' CMU wall.

The 5' wall will not be allowed to be located within the sight visibility triangles at the entrance from Columbia Street. See engineering comments.

Provide as a note on the plan stating that the new sliding gate will remain open during business hours.

2. Because of installing the wall, which limits the parking area to less than what was approved on the last site plan, this site will not be allowed to reduce the number of required parking spaces because of the change to the entrance from Columbia.

If the site is returned to the configuration of the last approved site plan, then because of the change to the entrance at Columbia the site then would be allowed to reduce the number of required parking spaces by how many parking spaces are actually lost. The site could possibly then be considered nonconforming. A letter from the zoning administrator approving nonconforming status for this site would be required to be obtained and submitted with the next submittal.

3. Per LUC Sec. 3.3.7.2 Table 3.3.7-I the minimum length of a parallel parking space is 23'. Plan indicates 6 parallel parking spaces along the east property line at 18' each. Revise plan.

4. The existing sign near the entrance from 6th Ave appears to overhang the adjacent parking space. Provide a detail clearly indicating the overhead clearance for the parking space.

5. A handicap ramp is required at the access aisle for the handicap parking spaces. In addition Truncated Dome (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

6. Clearly indicate the location of the handicap parking signs.

Per City of Tucson standards the minimum distance from grade to the bottom of the handicap sign is seven (7) feet. Clearly indicate.

7. Parking spaces will not be allowed to be located within the required landscape areas. See Landscape comments.

8. Provide copies of the last certificate of occupancy for the financial service use and the personal service use indicated on the plan. If the financial service use indicated is only an office and money is not exchanged it can be parked at 1:200 of GFA. Revise if required.

9. The parking calculations provided for the transportation land carrier appear to be incorrect. The required parking is based on the GFA of the office portion of the use only not the entire building. It appears that only one parking space would be required for this use. Revise calculations.

10. Remove the "credit for relocated southerly driveway - 5" from the parking calculations.

11. The PAAL width at the entrance from Columbia does not meet the requirements for a two way PAAL. Clearly indicate the direction of travel for the one way PAAL in this area.

12. Clearly indicate the location of the future curb and future sight visibility triangles along 6th Ave.

13. Provide distance and bearings for all property lines.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM00323.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
02/06/2008 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments.
03/04/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: March 3, 2008
SUBJECT: Site Plan
TO: Ruperto Cervantes/ Francisco Contreras
LOCATION: 4207 S 6th Avenue, T14S, R13E, Section 36, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM00323 (First Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan.

Site Plan:

1. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes per COT SD 207.
2. DS Sec.2-02.2.1.A.12: Clarify on the site plan that all handicap access ramps at crosswalks or at the transition of a pedestrian circulation area to a vehicular use area has the required detectable warning devices (truncated domes) per ANSI Standards A117.1-2003 Section 406.13.
3. Provide bearings on site plan per D.S. 2-02.2.1.5
4. DS Sec.2-02.2.1.A.10: Provide future site visibility triangles (SVTs), labeled and dimensioned. Refer to DS Sec.3-01.5.3 for line of site matrix for SVT.
5. Label egress and ingress include width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
6. Indicate curb returns for MS&R and call out radius on plans.
7. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
8. Fully dimensioned loading space maneuvering area(s) per D.S. 2-02.2.1.14.
9. Provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Provide estimated cut & fill quantities per D.S. 2-02.2.1.17. As part of the site submittal requirements the estimated cut and fill quantities are required to be indicated on the plans so that it is clear to the inspector that no cut in fill is to be taking place. If no cut and fill is taking place indicate the quantity of zero (0) on the plan. Estimated cut and Fill: Cut = 0 and Fill = 0 will suffice.
11. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
12. Label existing and future dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
13. DS Sec.2-02.2.1.A.18: Revise the site plan to call out 6th Avenue as a Major Streets and Routes (MS&R). Provide a note stating that the site plan is in conformance with the MS&R overlay zone criteria.
14. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for 6th Avenue and Columbia Street.
15. DS Sec.2-02.2.1.A.20: Verify that all easements for existing and proposed utilities (water, gas, electric) and public/private sewer lines are shown graphically on the plan together with recording docket and page reference. Reference all easements to detail and/or notes
16. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
17. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
18. Provide contour interval below the north arrow and scale on site plan.
19. Show Site Plan number in the lower right hand corner on all sheets per D.S. 2-02.2.1.29.
20. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Provide detail for refuse container - see enclosed detail Figure 3 for Solid Waste Disposal (Refuse).
21. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location.
22. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
23. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
24. List the consulting engineer on the plans along with the pertinent information (Name, Address and Phone Number). Provide phone number on site plan for owner.
25. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
26. All symbols on plans need to be indicated in legend. Indicate all symbols in legend.
27. Per the DNR violation case number T07DV12462 and the last approved site plan provided the 5' wall indicated as existing has not been permitted. Indicate on the plans the wall as being a new 5' CMU wall. Wall also appears to be located within the SVT - nothing over 30 inches in height is permitted within the SVT.
28. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2008 CPIERCE1 OUT TO CUSTOMER Completed