Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM00304
Parcel: 12701003S

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00304
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t08cm00304 2/12/08

1. Provide a cut sheet of the lighting fixture.
2. Provide TEP Available fault current.
3. Provide fault current rating of equipment.
4. Provide panel and circuit number for all lighting circuits.
5. Specify branch circuit conduit and conductor size and type.
6. Provide panel schedules with load calculations.
7. Specify service voltage.
02/14/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed