Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00304
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/12/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t08cm00304 2/12/08 1. Provide a cut sheet of the lighting fixture. 2. Provide TEP Available fault current. 3. Provide fault current rating of equipment. 4. Provide panel and circuit number for all lighting circuits. 5. Specify branch circuit conduit and conductor size and type. 6. Provide panel schedules with load calculations. 7. Specify service voltage. |
02/14/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |