Permit Number: T08CM00284
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM00284
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2008 PETER MCLAUGHLIN ZONING REVIEW Denied A separate Special Application for review and approval of the Scenic Corridor Zone (SCZ) overlay and Hillside Development Zone (HDZ) overlay is required. For more information contact Patricia Gehlen at 791-5608 ext 1179.
The overlay special application form is on the DSD website at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/Overlay_Zone_Application.pdf
The site plan may not be approved prior to Overlay Zone application approval. Add the Overlay Zone case number in the lower right corner of each sheet of the site plan, landscape, and NPPO plans. Also, when available, complete the information in Additional Note #7 on site plan sheet 1 of 7, including case number, date of approval and conditions.
12/01/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
12/01/2008 PETER MCLAUGHLIN NPPO REVIEW Approved
12/01/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied A separate Special Application for review and approval of the Scenic Corridor Zone (SCZ) overlay and Hillside Development Zone (HDZ) overlay is required. For more information contact Patricia Gehlen at 791-5608 ext 1179.
The overlay special application form is on the DSD website at http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/Overlay_Zone_Application.pdf
The site plan may not be approved prior to Overlay Zone application approval. Add the Overlay Zone case number in the lower right corner of each sheet of the site plan, landscape, and NPPO plans.
12/19/2008 JASON GREEN ENGINEERING REVIEW Denied HDZ and SCZ overlays still not submitted to CDRC. Verified with CDRC and Patricia Gehlen. I have called Mike Gardner, The Dirt Guy, LLC p: (520) 461-7076 www: azdirtguy.com, and commented that both the grading plan and site plan are due out on the 23rd and if the overlay aaplication are not submitted per my last comment letter then I will deny the projects with the same comments.

JG
12/19/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: December 22, 2008
SUBJECT: 4601 S Mission Road Site/Grading Plan- 3rd Engineering Review
TO: Coronado Engineering & Development, Inc; Attn: Paul Nzomo P.E.
LOCATION: T14S R13E Sec34 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM00284 (Site Plan) and T08BU00150 (Grading Plan)


SUMMARY: Engineering Division of Development Services Department has received the revised site plan (T08CM00284), Drainage Report (Coronado Engineering and Development, 30JAN08, revised 19AUG09, 25NOV08), Geotechnical Evaluation (LSI Group LLC, 05DEC07 addendum 21DEC07) and Stormwater Pollution Prevention Plan (Coronado Engineering and Development, 28JAN08, revised but not signed or sealed) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading plan at this time. The following items need to be addressed:


SITE PLAN, GRADING PLAN and DRAINAGE REPORT COMMENTS:

The Drainage Report submitted for this project can not be shown to be in conformance with DS Sec.10-01 and 10-02. A meeting is required with the Development Services Engineering Administrator, Development Services Engineering Reviewer, the project engineer and the Civil Engineer who stamped the report and plans. The HEC-RAS model submitted does not conform to the Development Standards and does not accurately reflect the proposed encroachment into the regulatory 100-year floodplain, the critical basin requirements have not been adequately addressed, the Environmental Resource Report has not been submitted, etc.

The HDZ and SCZ Overlay applications will be reviewed under a separate letter and all comments associated with them will be posted when the correct information is submitted to the CDRC Department in order to submit the application for review.

Please refer to Jim Vogelsberg, Engineering Administrator for any additional questions regarding this project.


GENERAL COMMENTS:

A meeting is required to discuss this project with the Engineering Division, the Project Engineer and the consultant to help expedite the resubmittal prior to resubmitting the plans. I can be reached at 837-4929 to schedule that meeting.

Further comments may be generated upon resubmittal of the SCZ, HDZ and site plan review.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
12/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
02/02/2009 SUE REEVES REJECT SHELF Completed