Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00267
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/19/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Complete recirculation of ventilation air from toilet rooms is prohibited. Interlocking the exhaust fan with the light switch will result in complete recirculation of the ventilation air to the toilet room whenever the light is turned off. Reference: Section 403.2.1 (3), IMC 2006. |
| 05/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/02/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |