Permit Number: T08CM00267
Parcel: 133369690

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00267
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Complete recirculation of ventilation air from toilet rooms is prohibited. Interlocking the exhaust fan with the light switch will result in complete recirculation of the ventilation air to the toilet room whenever the light is turned off. Reference: Section 403.2.1 (3), IMC 2006.
05/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved