Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00267
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/07/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED SITE PLAN OF EXISTING CENTER SUBMITTED SHOWING PROJECT LOCATION AND ALL ACCESSIBILITY ROUTS TO SPACE WITH SLOPES AS PER ANSI 117.1. IDENTIFY THE SPACE AND IDENTIFY THE ROUTES AND IDENTIFY THE PARKING SPACES AND THEIR ROUTES. 2. CANNOT ACCESS TOILET THROUGH KITCHEN; IBC SECTION 2902.4, THIS HAS NOT BEEN APPROVED BY CITY 3. PROVIDE STATEMENT ON DRAWINGS THAT WATER WILL BE PROVIDED UPON CUSTONMER REQUEST AND THAT A SUPPLY OF PAPER CUPS IS PROVIDED AT COUNTER 4. MINIMUM SIZED LETTERING ON ALL DRAWINGS TO BE 1/8", 3/32" IS ACCEPTABLE ONLY WITH AN APPEAL APPROVAL FROM THE BUILDING OFFICIAL ACCEPTING 3/32" |
04/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed; the reference shell drawing (M-1) shows an incomplete mechanical system. Provide a mechanical plan to show how the existing mechanical system will be modified for the new occupancy. Reference: Section 106.3.1, IMC 2006. 2. Comment not addressed. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006. 3. Section 504.4, IMC 2006 requires a dryer exhaust to be equipped with a backdraft damper. Provide the listing information for the dryer vent cap called out in detail 5/P1. Reference: Section 106.3.1, IMC 2006. 4. Comment not addressed. Show how the dryer installation complies with Section 504.5, IMC 2006. |
04/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans (i.e. P1) sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Eliminating the required shut-off valve for the water heater is not an acceptable solution to the problem of having a valve located between the water heater and the expansion tank. See Sections 605.4, 608.3, and 608.7, UPC 2006 for the plumbing requirements associated with the installation of a water heater. 3. If P13 (drinking fountain) is to be eliminated from the project, show how and where the waste, vent, and water piping associated with the fixture is to be terminated. Reference: Section 103.2.3, UPC 2006. |
04/24/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide cut sheets for neon signs. Reference Sheet E1. This comment was made on the first submittal. Plans indicate junction boxes for hardwired connection. Please clarify. 2. Registrant shall seal, sign, and date drawings. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/05/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
05/05/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
05/05/2008 | GERARDO BONILLA | REJECT SHELF | Completed |