Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00263
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The hazard classification of the building, including any special hazards. 3. The density required of the water supply. |
| 10/15/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/15/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. COUNTRY INN & SUITES - 636FU @ SFR RATE - 515FU @ COMMERCIAL RATE 2. NEEDS ADDRESSING REVIEW 3. NEEDS WASTEWATER 8TH FLOOR CAPACITY REVIEW 4. NEEDS WASTEWATER 8TH FLOOR REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER THRU ADJACENT PROPERTY 5. NEEDS MANHOLE TAP PERMIT - 100 N STONE AV - 617-8228 6. NEEDS TO PERMIT ON - SITE PRIVATE SEWER - NEED DEQ REVIEW & APPROVAL IF OVER 3000 GALLONS/DAY |
| 10/23/2008 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approved | DATE: October 23, 2008 TO: Kent Delph, PE, Grenier Engineering SUBJECT: Country Inn Hotel Floodplain/Site/Grading Plan Engineering Resubmittal Review LOCATION: 665 N Freeway Rd ACTIVITY NUMBERS: T08CM00263 / T08BU00131 / T08OT01399 SUMMARY: Engineering has received and reviewed the revised Grading Plan package with the Floodplain Use Permit application for review of the Country Inn & Suites Building addition. The Grading and Floodplain Use Permit applications are approvable by Engineering. If there are any questions, you may contact me at 837-4934. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/31/2008 | VFLORES1 | OUT TO CUSTOMER | Approved |
| 10/31/2008 | SUE REEVES | REJECT SHELF | Completed |