Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T08CM00263
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2008 | HEATHER THRALL | ZONING | REVIEW | Denied | TO: Development Services Department, Plans Coordination Office FROM: Heather Thrall, Senior Planner PROJECT: T08CM00263, 665 N. Freeway, New Country Inn Hotel, 2nd Review TRANSMITTAL DATE: August 1, 2008 COMMENTS: Please resubmit revised drawings and response letter addressing all Zoning Review comments OR email me for a counter appointment after all other divisions have completed review of this submittal. 1. This comment has not been addressed. A cross access agreement is required. Per DS 2-02.2.1.11, regarding PAALs A) A cross ACCESS agreement is required between existing hotel and new hotel, as plan shows access to parking for existing Ramada Inn via travel across Country Inn site. Provide copy & note cross access agreement and recordation information on plan. 2. Per DS 2-02.2.1.12, regarding handicapped and pedestrian circulation: B) Response indicates a pedestrian connection provided to adjacent Ramada Inn, per DS 2-08.4.1. It is difficult to determine how connection accomplished to Ramada Inn pedestrian route. Appears on drawing the crosswalk just leads to parking space for the adjacent hotel. Provide a keynote for this area to cross reference to detail 6/C-3. 3. Per DS 2-02.2.1.20, please provide docket and page for water easement. 3. I may be reached at Heather.Thrall@tucsonaz.gov or at 837-4951. IF YOU PREFER, I AM WILLING TO DO A FINAL REVIEW IN A MEETING. EMAIL ME FOR A TIME. HCT C:\planning\site\DSD\T08CM00263 665 N. Freeway 2.doc |
| 08/08/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 08/21/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: August 21, 2008 TO: Kent Delph, PE, Grenier Engineering SUBJECT: Country Inn Hotel Grading Plan Engineering Resubmittal Review LOCATION: 665 N Freeway ACTIVITY NUMBER: T08BU00131, T08CM00263, T08OT0 SUMMARY: Engineering has received and reviewed the revised Grading Plan package for review of the Country Inn & Suites Building addition. The plan is not approved at this time. Address the remaining comment: GRADING PLAN COMMENT: 1) DS Sec.2-02.2.1.20: All Easement data is required for Engineering approval for the grading plan. Show all easements on the plan with docket and page. On utility sheet, clarify the individual utility lines. If there are any fiber optic lines must be identified and notated. Specifically, provide the Dkt and pg for the 20-ft water easement on sheet 6. 2) Resubmittal may be required if registrant does not add information (above) at the counter. Submit the resubmittal package to the permit clerks under T08BU00131 including: a) 2 copies of the revised grading plan. b) 2 copies of the revised SWPPP c) 2 copies of Geotechnical report and any addenda. d) 2 copies of revised drainage report. e) Floodplain Permit application and fee. f) Response letter. Address the easement comment for engineering approval. If there are any questions, you may contact me at 837-4934. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |