| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/24/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00235 1/24/08 1. Please provide load calculations on Panel A. 2. Indicate location of Panel A on plans. 3. Provide panel schedule for New Panel, as depicted on One-Line Diagram and on plans. Include fault calculations and fault current rating. 4. Provide conduit and conductor size and type for New Panel. |
| 01/24/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/24/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |