Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/16/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide the manufacturer's listing information for the batch freezer, E6, to clarify how the two water connections will be used. Reference: Section 103.2.3, UPC 2006. 2. Comment not addressed. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 3. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. |
05/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/30/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/30/2008 | SHANAE POWELL | REJECT SHELF | Completed |