Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide the manufacturer's listing information for the batch freezer, E6, to clarify how the two water connections will be used. Reference: Section 103.2.3, UPC 2006.
2. Comment not addressed. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
05/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved