04/11/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ALL LETTERING TO BE MINIMUM OF 1/8" HIGH, OR OBTAIN VARIANCE IN WRITING FROM BUILDING OFFICIAL.
2. PROVIDE STRUCTURAL CALCULATIONS FOR WATER HEATER SUPPORT.
04/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Comment not addressed. Provide a copy of the approved shell building drawings for reference. Reference: Section 106.3.1, IMC 2006.
3. Comment not addressed. Clarify the ventilation calculations with regard to which code is being used to determine the required amount of outside air, i.e. ASHRAE 62.1-2004 or IMC 403.3. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Note that the "lobby" of the suite is not a "retail sales floor".
04/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Comment not addressed. Provide a copy of the approved shell building drawings for reference. Reference: Section 103.2.3, UPC 2006.
3. Comment not addressed. The existing 2" service to the building is not capable of accommodating a demand of 100 GPM without exceeding the maximum velocity of 8 FPS. Reference: Section 610.12, UPC 2006.
4. Comment not addressed. Provide the manufacturer's listing information for the batch freezer, E6, to clarify how the two water connections will be used. Reference: Section 103.2.3, UPC 2006.
5. Comment not addressed. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
6. Comment not addressed. Provide a floor drain in the kitchen. Reference Sections 411.2.2 and 704.3, UPC 2006.
7. Comment not addressed. The fixture schedule on sheet A-2 calls for the installation of an electric water cooler, X10. Coordinate the plumbing and architectural designs. Note that a drinking fountain will have to comply with the requirements of Section 1109.5, IBC 2006.
04/24/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved