Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00231
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SITE PLAN IS ILLEGABLE 2. NEED DUAL LEVEL WATER FOUNTAIN AS PER IBC 2006 SECTION 2902, TABLE 2902.1, ITEM 6 AND ANSI 117.1 SECTION 602.4 3. ALL LETTERING TO BE MINIMUM OF 1/8" HIGH 4. PROVIDE STRUCTURAL ENGINEER DETAILING AND CALCULATIONS FOR WATER HEATER SUPPORT |
| 01/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/23/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/24/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Provide a copy of the approved shell building drawings for reference. Reference Section 106.3.1, IMC 2006. 3. Clarify the ventilation calculations with regard to which code is being used to determine the required amount of outside air, i.e. ASHRAE 62.1-2004 or IMC 403.3. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Note that the "lobby" of the suite is not a "retail sales floor". |
| 02/06/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/07/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Provide a copy of the approved shell building drawings for reference. Reference Section 103.2.3, UPC 2006. 3. The existing 2" service to the building is not capable of accommodating a demand of 100 GPM without exceeding the maximum velocity of 8 FPS. Reference Section 610.12, UPC 2006. 4. Provide the manufacturer's listing information for the batch freezer, E6, to clarify how the two water connections will be used. Reference Section 103.2.3, UPC 2006. 5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 6. Provide a floor drain in the kitchen. Reference Sections 411.2.2 and 704.3, UPC 2006. 7. The fixture schedule on sheet A-2 calls for the installation of an electric water cooler, X10. Coordinate the plumbing and architectural designs. Note that a drinking fountain will have to comply with the requirements of Section 1109.5, IBC 2006. |
| 02/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. The Series Rating Notes, #31 on Sheet 1815, are redundant to the fully rated panels at this location. Please remove. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 3. One-Line Diagram calls for all new utility meters. This does not appear to be necessary for the Cold Stone Creamery occupancy. 4. It appears that all panels are existing with the exception of new Panels CSC and CSC2. Please clarify this on the line diagram |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/15/2008 | SUE REEVES | REJECT SHELF | Completed |