Permit Number: T08CM00217
Parcel: 123140450

Address:
842 E SENECA ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM00217
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM00217

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

STRUCTURAL PLANS:

1. Provide manufacturer's calculations and data for pre-engineered trusses consistent with the plans, R106.1. Truss calculations differ from the plans for span and support points, R802.10.2.

PLUMBING PLANS:

1. Revise the gas line isometric showing the point of connection, branch length and demand of each appliance, UPC 1217.2, & Table 12-8.

ELECTRICAL PLANS:

1. Kitchen receptacles shall be on a separate 20 AMP circuit (#11) with no outlets at other locations (Garage), E3801.3.1. Show Garage receptacle on a different circuit.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2008 CINDY AGUILAR APPROVAL SHELF Completed
05/30/2008 CINDY AGUILAR OUT TO CUSTOMER Completed