Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00207
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
02/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The architectural draqwings call for a hi-low drinking fountain in order to comply with Section 1109.5, IBC 2006 but a single drinking fountain is shown and specified on the plumbing plans. 2. Provide the shell drawings for comparison with the TI package. |
02/21/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
02/21/2008 | GBONILL1 | WWM | REVIEW | Needs Review |