Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00189
Parcel: 12810082A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00189
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied As noted in the previous comments, given that the temperature range of the water supply in Tucson is as high as 90.3 degrees Fahrenheit, specify how the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
04/18/2008 SHANAE POWELL REJECT SHELF Completed