Permit Number: T08CM00189
Parcel: 12810082A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00189
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide listing information for the "Symmons S160 blending valve". Indicate on the drawings the maximum temperature setting for the hot water supply to the public lavatories. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Comment not resolved; provide the developed pipe length for the water supply piping. Reference Sections 610.4 and 610.5, UPC 2006.
3. Comment not addressed. Provide upper terminal cleanouts for P4 and P5. Reference: Section 707.4, UPC 2006.
04/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved