Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00189
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/08/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the "Symmons S160 blending valve". Indicate on the drawings the maximum temperature setting for the hot water supply to the public lavatories. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Comment not resolved; provide the developed pipe length for the water supply piping. Reference Sections 610.4 and 610.5, UPC 2006. 3. Comment not addressed. Provide upper terminal cleanouts for P4 and P5. Reference: Section 707.4, UPC 2006. |
| 04/08/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |