Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00189
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/25/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/26/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Condensate drains may not terminate over a roof drain unless the roof drain terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
03/26/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show how installing the air gap fitting with a continuous waste connection to the tailpiece of P4 complies with Section 1001.2, UPC 2006. Reference: Section 103.2.3, UPC 2006. 2. Comment not addressed. Considering the wide range of water supply temperatures in Tucson, show how the temperature of the hot water supply to the public lavatories is to be set on the faucet limit stops. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 3. Comment not resolved; provide design pressure calculations and developed pipe length. Provide calculations showing how the water supply piping has been sized. Reference Sections 610.4 and 610.5, UPC 2006. 4. Comment not addressed. Provide upper terminal cleanouts for P4 and P5; show the cleanout for the toilet chase on the riser diagram. Reference: Section 707.4, UPC 2006. 5. Comment not addressed. Correct the natural gas branch pipes to the new RTU's. Reference Sections 103.2.3 and 1217.0, UPC 2006. |
03/31/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/02/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 2. Demonstrate compliance with the 2006 IECC. 3. Add Lighting Fixture XW, on building exterior, to the Lighting Fixture Schedule. 4. Load KVA for Exterior Lights on H21A-17, 0.00, not reasonable. 5. Provide Panel Schedule H21B. Lighting Plan has devices circuited to 6 and 8. 6. Emergency lighting appears to violate NEC 700.12 (F). 7. RTU-1 is on H21A-40,42 on the Power Plan, but appears to be on H21A-36,38 Panel Schedule. Please correct in this case, and in all others which may apply. 8. Leak Detection and Condensate Pump on Keynote 14 Sheet E03.01 is on R21B-13. This is a spare on the Panel Schedule. 9. RTU-2, RTU-3 and RTU-4 take 35A Maximum Overcurrent Protective Device per Packaged Roof Air Handler Schedule on Sheet H08.01. Circuit Breakers are 40A. 10. Address the requirements of NEC 410.73 (G), as necessary. Willing to discuss. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/08/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
04/08/2008 | SHANAE POWELL | REJECT SHELF | Completed |