Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00189
Parcel: 12810082A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00189
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 PAUL MACHADO ENGINEERING REVIEW Approved
02/28/2008 MARTIN BROWN FIRE REVIEW Denied Per 2006 IFC, table 1019.2, travel distance for buildings with one exit is limited to 75'. Plans indicate 90' travel distance.
The exception for not requiring rated corridors (section 1017, #4) does not apply.
02/28/2008 GERRY KOZIOL WWM REVIEW Approved
02/29/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Include a separate architectural site plan showing all site amenities:
a. Drive and walkways
1. All accessible routes from public transportation to the accessible front entrances are to be identified
2. All accessible routes from accessible parking spaces to accessible front entrances are to be identified
3. Slopes for all accessible routes are to be noted and further clarified by providing spot elevations at appropriate locations to evaluate slope design
b. Parking layout
1. Show accessible spaces plus spot elevations for slope compliance
c. Paved areas and types of paving
d. Building footprint and configuration with entrances and exists identified
e. Landscape areas
f. Property lines
g. Streets, easements and R.O.W.s
h. Fences, curbs, ponding areas, drainage structures and etc
i. Dimension all elements of construction shown on the site plan
2. Incorrect dimensions shown for vertical grab bar, ref ANSI 117.1 604.5.1
3. Corridor design shown presents a single enity exit corridor systm for all 49 occupants of building. With no sprinklers, maxium corridor load is 30. Corridor must be 1 hour rated.
03/18/2008 CAGUILA1 WATER REVIEW Needs Review
03/18/2008 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
03/18/2008 CAGUILA1 ZONING REVIEW Needs Review
03/18/2008 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
03/18/2008 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review