Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00189
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED DETAILED ARCHITECTURAL SITE PLAN SHOWING DIMENSIONS AND ALL EMINITIES INCLUDING ACCESSIBLE PATHS AND PARKING 2. NEED CODE REVIEW CHECK LIST COMPLETED AND SUBMITTED WITH/ON PLANS. REFERENCE CITY OF TUCSON, DSD/PERMITS WEB SITE 3. NEED VERTICAL GRAB BAR AT TOILETS, REFERENCE ANSI 117.1, SECTION 604.5.1 4. SHOW EXPOSED PIPE BELOW LAVRATORY TO BE COVERED AS PER ANSI 117.1, SECTION 606.6 5. OCCUPANT LOAD INCORRECTLY CALCULATED WITH TENANT/USUABLE AREA. TABLE 1004.1.1 SPECIFIES GROSS SQUARE FEET. 6. MAXIUM TRAVEL DISTANCE FOR BUSINESS, NON SPRINKLERED IS 200' NOT 300' AS SHOWN 7. IN REFERENCE TO SWITCHES AND CONTROLS, OPERATABLE PARTS SHALL BE LOCATED AT A HEIGHTS AS DESCRIBED IN ANSI 117.1.1, SECTION 309. 8. MINIMUM HEIGHT OF DRAWING LETTERING FONTS IS TO BE 1/8". 9. IF BUILDING IS NOT SPRINKLERED AS INDICATED, ALL EXIST CORRIDORS MUST BE 1 HOUR RATED AS PER IBC 2006, SECTION 1017 AND TABLE 1071.1 |
01/22/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/23/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Indication on plans is that building does not contain fire sprinklers. Please verify. If this is true, corridors will need to be 1 hour rated. |
01/24/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | needs 5th floor credit evaluation if applicable. needs to show removal of plumbing fixtures if applicable |
01/28/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
01/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Correct the address used on the drawings (5330, not 5530 E. Broadway Blvd.) and the location map. 3. Provide the civil drawings referenced on sheet P02.01 to show the site work. 4. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 2006. 5. Show the waste piping for P-4 on the plumbing plan. Reference Section 103.2.3, UPC 2006. 6. Clarify the termination of the drain from the drip pan for the chiller as shown in detail 2/P01.01. Reference Section 103.2.3, UPC 2006. 7. Clarify the connection of the chiller supports to the roof assembly; the architectural drawings (e.g. A07.02) indicate a truss construction, not a structural slab. Reference Section 103.2.3, UPC 2006. 8. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Sections 310.0 and 314.5, UPC 2006. 9. Provide floor drains in the restrooms. Reference Section 411.2, UPC 2006. 10. Show that the floor of each restroom slopes toward the floor drain. Reference Section 411.2, UPC 2006. 11. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 12. Provide calculations showing how the water supply piping has been sized. Reference Sections 610.4 and 610.5, UPC 2006. 13. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2006. 14. Revise the natural gas piping shown on sheet P02.01 to show the developed lengths of the piping. Reference Sections 103.2.3 and 1217.0, UPC 2006. |
01/30/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. 2. Correct the address used on the drawings (5330, not 5530 E. Broadway Blvd.) and the location map. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference Section 503.2, IECC 2006. 4. Provide the installed weight of the rooftop equipment. Reference Section 106.3.1, IMC 2006. 5. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 302.1, IMC 2006. 6. Show the size, routing, and termination of all of the new condensate drains. Reference Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 7. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2006. 8. Clarify the return from the electrical room (116). If it is a plenum return, does the plenum comply with Section 602, IMC 2006? |
02/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 8. RTU-1 takes 25A Maximum Overcurrent Protective Device per Packaged Roof Air Handler Schedule on Sheet H08.01. Circuit Breaker is 30A |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/28/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
02/28/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
02/28/2008 | DELMA ROBEY | REJECT SHELF | Completed |