Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM00186
Parcel: 13609014B

Address:
10355 E 29TH ST

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T08CM00186
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NUMBER OF BLOCKS (126) REQUIRED PER THE CALCULATIONS TO RESIST OVERTURNING/SLIDING OF THE CHIMNEY DOES NOT AGREE WITH THE NUMBER OF BLOCKS (96) SHOWN ON SECTION 4 OF SHEET S-2.
2. CALCULATE DEFLECTION OF EXISTING JOISTS UNDER NEW LOADS AND COMPARE TO ALLOWABLE PERMITTED.
01/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2008 Michael Wyneken PLANNING-CITY HALL REVIEW Denied The height to the top of the fiberglass chimney screen panel is shown on sheet C4 as being measured from the finished floor elevation. Special Exception condition #5 states the height is to be measured from the finished grade, which is the how height is measured per the Tucson Land Use Code. The condition was added to specifically alert the designer to this Code provision. The drawing must be revised to show the overall height of the chimney from the finshed grade. The chimney is close to maximum allowed height, so this is a critical point.
02/13/2008 JAY HOGAN COMMUNICATIONS REVIEW Approved
02/13/2008 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T08CM00186, 10355 E. 29th St.,
Cell Tower, new equip on existing church site, Site Review
1st Review

TRANSMITTAL DATE: February 13, 2008

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project was reviewed for compliance with the Land Use Code (LUC) and Development Standards (DS).

2. Per LUC 2.2.4 and the last approved site plan for this property, the maximum allowed lot coverage is 50%. The church property development was at 49.99% - without the two sheds that have since been erected without plan approval or permits. Further, the proposed easement for the service to the equipment area, is a vehicular use area, which counts towards lot coverage, as defined by the LUC. The proposal would exceed 50%, and the site is already exceeding 50% with the two shed structures. The project requires a re-design for access to the equipment area without increasing lot coverage, and the sheds will require removal as well.

3. Until the above is addressed, and Planning affirms all other special exception requirements have been met, zoning will not be able to approve the proposal.

4. I may be reached at Heather.Thrall@tucsonaz.gov or at 520-837-4951.



If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\T08CM00186.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
02/22/2008 SHANAE POWELL REJECT SHELF Completed