Permit Number - T08CM00184
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/18/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/18/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/18/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00184 1/18/08 1. Provide fault calculations at new panel. 2. Provide location of 4 ton HP on plans, both mechanical and electrical. On the other hand, if this is existing equipment, please state so on the panel schedule. 3. Note on Sheet E2.0 documents an existing feeder of 200A, whereas the #2 feeder to the new panel has a 155A ampacity. Please clarify. 4. Please provide Fixture Schedule for new lighting. |
| 01/18/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/18/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/18/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/20/2008 | VFLORES1 | WWM | REVIEW | Needs Review |