Permit Number: T08CM00184
Parcel: 10510062G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00184
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 HEATHER THRALL ZONING REVIEW Approved
01/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/18/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00184 1/18/08

1. Provide fault calculations at new panel.
2. Provide location of 4 ton HP on plans, both mechanical and electrical. On the other hand, if this is existing equipment, please state so on the panel schedule.
3. Note on Sheet E2.0 documents an existing feeder of 200A, whereas the #2 feeder to the new panel has a 155A ampacity. Please clarify.
4. Please provide Fixture Schedule for new lighting.
01/18/2008 ROBERT SHERRY WATER REVIEW Approved
01/18/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/18/2008 PAUL MACHADO ENGINEERING REVIEW Approved
01/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/18/2008 MARTIN BROWN FIRE REVIEW Approved
01/18/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/20/2008 VFLORES1 WWM REVIEW Needs Review