Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00184
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
01/18/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/18/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00184 1/18/08 1. Provide fault calculations at new panel. 2. Provide location of 4 ton HP on plans, both mechanical and electrical. On the other hand, if this is existing equipment, please state so on the panel schedule. 3. Note on Sheet E2.0 documents an existing feeder of 200A, whereas the #2 feeder to the new panel has a 155A ampacity. Please clarify. 4. Please provide Fixture Schedule for new lighting. |
01/18/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/18/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/18/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
01/18/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
01/18/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/18/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/20/2008 | VFLORES1 | WWM | REVIEW | Needs Review |