Permit Number: T08CM00178
Parcel: 120080920

Address:
4519 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00178
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 JASON GREEN ENGINEERING REVIEW Approved
02/01/2008 TERRY STEVENS ZONING REVIEW Approved
02/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the condition of the wall located behind the hood. The drawing does not indicate the wall construction nor does it indicate how the window will be addressed or how the wall surface will comply with Section 507.9, IMC 2006.
2. The structural drawings shall be part of the drawing set.
3. Show that the construction of the make up air complies with Section 506.3.1.2, IMC 2006.
4. Show how the location of the new exhaust fan complies with with Section 506.5, IMC 2006.
5. Show how the new evaporative cooler is to be drained and the termination point of the drain.
4. Revise the minimum font size to 1/8" (all upper case).
02/01/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2008 ROBERT SHERRY WATER REVIEW Approved
02/01/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ADD DRAWINGS FROM CALCULATIONS TO THE DRAWING SET SHOWING EXISTING BEAM REVISION FOR MECHANICAL SUPPORT.
2. FIX WINDOW POSITION.
02/01/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved .
02/01/2008 DAVE MANN FIRE REVIEW Approved
03/20/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved