Permit Number: T08CM00177
Parcel: 14001050A

Review Status: Completed

Review Details: SITE

Permit Number - T08CM00177
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2008 MARTIN BROWN FIRE REVIEW Denied Show fire hydrant location per IFC 508. Fire sprinklers are required if distance exceeds 300 feet.
01/25/2008 ANDREW CONNOR NPPO REVIEW Denied Provide acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property per DS 2-15.2.0.C.
01/25/2008 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Revise the landscape plans to show the limits of grading. DS 2-07.2.2.B.5.

2. A vehicular use area must be provided with post barricades or wheel stop curbing to prevent parked vehicles from extending beyond the property lines; damaging adjacent landscaping, walls, or buildings and to prevent vehicles from driving onto unimproved portions of the site per DS 3-05.2.3.C. Revise the plans as necessary.

3. Identify any portion(s) of the site used for outdoor storage. All outdoor storage areas must be screened per LUC 3.7.2-I.

4. All disturbed grubbed, graded, or bladed areas not otherwise improved shall be landscaped, reseeded, or treated with an inorganic or organic ground cover to help reduce dust pollution. Revise landscape plan to identify the type and all the locations proposed for inert ground cover materials or seeded areas per LUC 3.7.2.7.

5. Show and identify existing plants to remain in place on the landscape plan. DS 2-07.2.2.A.1.e.

6. Provide acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property per DS 2-15.2.0.C.

7. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation. Verify on the site and landscape plan water lines and irrigation point of connection.

8. Trees and shrubs are to be selected and located so that, at maturity, they do not interfere with existing on-site or off-site utility service lines or utility easements LUC 3.7.2.6.B.
Sewer line appear to be in planting areas for the required landscaping.

9. Additional comments may apply.
01/28/2008 STEVE SHIELDS ZONING HC SITE REVIEW Denied See zoning comments
01/28/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Dusty Duds Excavating
T08CM00177
Site Plan (1st Review)

TRANSMITTAL DATE: January 28, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. D.S. 2-02.2.1.A.2 Provide a property description (legal description) on the plan.

3. D.S. 2-02.2.1.A.5 Please clarify the lot dimensions and bearings for the west property line.

4. D.S. 2-02.2.1.A.7 Provide a dimension for the required street setback. This dimension is based on LUC Section 3.2.6.5.A and measured from the property line.

5. D.S. 2-02.2.1.A.8 Fully dimension the parking layout, i.e. parking area access land (PAAL), back-up spur, etc.

6. D.S. 2-02.2.1.A.8 Per ICC/ANSI A117.1-2003 Section 502.5 Floor Surfaces show the maximum slopes allowed for the accessible vehicle parking space and access aisle on detail 2/C-1.

7. D.S. 2-02.2.1.A.8 Detail 3/C-1 ACCESSIBLE PARKING SIGN, the height dimension for the sign is not correct. This dimension should be 7'-0".

8. D.S. 2-02.2.1.A.11 Provide a dimension for the PAAL between the proposed sidewalk and the vehicle parking spaces.

9. D.S. 2-02.2.1.A.12 Detectable warnings (truncated domes) are required at the accessible access aisle and sidewalk area. See ICC/ANSI A117.1-2003 Section 406.13 for truncated dome requirements.

10. D.S. 2-02.2.1.A.12 Per D.S. 3-05.2.3C.1 some type of barrier is required to prevent vehicles from driving onto unimproved portions of the site. This said some type of barrier is required at the southeast end of the proposed parking areas back-up spur.

11. D.S. 2-02.2.1.A.13 If applicable provide the location, type, size and height of existing and proposed freestanding signage and billboards.

12. D.S. 2-02.2.1.A.19 Provided dimensions for the right-of-way (ROW).

13. D.S. 2-02.2.1.A.20 If applicable show all easements of record graphically on the plan together with recording docket and page reference.

14. D.S. 2-02.2.1.A.25 If applicable provide existing and proposed freestanding lighting layout and type. Provide a detail; list the height of pole and type of lighting.

15. D.S. 2-02.2.1.A.28 Show the existing zoning for all adjacent parcels on the plan.

16. D.S. 2-02.2.1.A.31 Revise the proposed use to read "CONSTRUCTION SERVICES".

17. D.S. 2-02.2.1.A.32 Zoning acknowledges the location proposed for the refuse container. Provide pavement for the access and maneuvering area for the refuse container. Per D.S. 3-05.2.3C.1 some type of barrier is required to prevent vehicles from driving onto unimproved portions of the site. This said show the required barriers on the plan.

18. D.S. 2-02.2.2.3 Provide the proposed Floor Area Ratio (FAR) on the plan.

19. D.S. 2-02.2.2.4 Under the "REQUIRED PARKING" the use of "office" should read "CONSTRUCTION SERVICES".

20. D.S. 2-02.2.2.4 The provided bicycle parking calculation in not correct. Per LUC Sec. 3.3.3.5 the minimum number of bicycle parking spaces is two (2). Revise the calculation to reflect "2 sp req'd."

21. This project is located within the Davis-Monthan Air Force Base Airport Hazard District. Provide a note on the plan stating "THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE CRITERIA: LUC, SEC. 2.8.5 AIRPORT ENVIRONS ZONE (AEZ)". Also provide a building height as it relates to the Median Sea Level (MSL), see LUC Section 2.8.5.11.

22. Provide documentation that supports the future ROW shown on the plan.

23. Zoning acknowledges the proposed "FUTURE BLDG's" shown on the site. These proposed buildings will require site plan review.

24. Ensure all changes to the site plan are reflected on the landscape plan.

25. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t08cm00177

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
02/26/2008 LOREN MAKUS ENGINEERING REVIEW Denied February 28, 2008
T08CM00177
Site Plan Review
Loren Makus, EIT

1. Clearly indicate the limits of development for this site.
2. Show all areas that will be used for equipment and material storage. All vehicle use areas must be paved.
3. Show how the solid waste enclosure will be accessed by the solid waste service vehicle. The approach and maneuvering area must be paved. If the enclosure is to be serviced by City of Tucson Solid Waste trucks, the pavement should be constructed to withstand the weight of the loaded trucks.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2008 CPIERCE1 OUT TO CUSTOMER Completed
04/16/2008 SHANAE POWELL REJECT SHELF Completed