Permit Number: T08CM00174
Parcel: 12706010A

Address:
40 N SWAN RD 02

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00174
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved 1. Provide load calculations for the large distribution panel and the SES. Please add electrical load for this project, to totals from the Service Entrance (separate contract). For example: Total for 800A distribution panel, from Service Entrance drawings sealed by Jeff Matthews, 5/6/08: 667A. This project 91 A. New Total 758A. Total for entire service, from Service Entrance drawings sealed by Jeff Matthews, 5/6/08: 1302A. This project 91 A. New Total 1393A.
2. Please annotate "GFCI" by new pit, cab, and equipment room receptacles. This is required by NEC 620.85. We have been letting it go on the plans, but lately certain contractors are starting to dispute this in the field.
3. Demonstrate that new equipment room qualifies as a separate building.
05/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved