Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00174
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 1. Provide load calculations for the large distribution panel and the SES. Please add electrical load for this project, to totals from the Service Entrance (separate contract). For example: Total for 800A distribution panel, from Service Entrance drawings sealed by Jeff Matthews, 5/6/08: 667A. This project 91 A. New Total 758A. Total for entire service, from Service Entrance drawings sealed by Jeff Matthews, 5/6/08: 1302A. This project 91 A. New Total 1393A. 2. Please annotate "GFCI" by new pit, cab, and equipment room receptacles. This is required by NEC 620.85. We have been letting it go on the plans, but lately certain contractors are starting to dispute this in the field. 3. Demonstrate that new equipment room qualifies as a separate building. |
| 05/22/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved |