Permit Number: T08CM00174
Parcel: 12706010A

Address:
40 N SWAN RD 02

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM00174
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/22/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide the 15A fuses in the disconnects for AH-1 and HP-1. Reference Sheet M0.1.
2. Provide load calculations for the large distribution panel and the SES.
3. Address the grounding requirements per NEC 250.32 Second Building/Structure.
4. Address the disconnecting means and number of supplies for this Second Building per NEC 225 Part II.
5. Elevator Room lighting and receptacle shall be on the same electrical circuit. Reference NEC 620.23 (A).
6. Provide for the branch circuit/s as necessary per NEC 620.22.
7. Provide for the branch circuit/s as necessary per NEC 620.24.
02/20/2008 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2008 CPIERCE1 OUT TO CUSTOMER Completed