Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM00174
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/22/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 02/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide the 15A fuses in the disconnects for AH-1 and HP-1. Reference Sheet M0.1. 2. Provide load calculations for the large distribution panel and the SES. 3. Address the grounding requirements per NEC 250.32 Second Building/Structure. 4. Address the disconnecting means and number of supplies for this Second Building per NEC 225 Part II. 5. Elevator Room lighting and receptacle shall be on the same electrical circuit. Reference NEC 620.23 (A). 6. Provide for the branch circuit/s as necessary per NEC 620.22. 7. Provide for the branch circuit/s as necessary per NEC 620.24. |
| 02/20/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/21/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |