Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM00154
Parcel: 14002010A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T08CM00154
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2008 CAGUILA1 WWM REVIEW Needs Review
01/16/2008 CAGUILA1 ENGINEERING REVIEW Needs Review
01/16/2008 CAGUILA1 FIRE REVIEW Needs Review
01/16/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/16/2008 CAGUILA1 WATER REVIEW Needs Review
02/18/2008 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
02/20/2008 CAGUILA1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2008 CINDY AGUILAR OUT TO CUSTOMER Completed