Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00152
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/16/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
01/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/16/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/16/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/16/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/16/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
01/16/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide information to show that the addition of the new fixtures will not result in overloading the existing drain piping. Reference Section 101.5.1 and footnote 4, Table 7-5, UPC 2006. |
01/16/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
01/17/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
01/17/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |