Permit Number: T08CM00131
Parcel: 135021330

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM00131
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/30/2008 DAVE MANN FIRE REVIEW Approved
01/30/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PLEASE PROVIDE APPROVED BUILDING OFFICAL APPEAL FOR 3/32" FONT
2. CLARIFY HEIGHT OF DRINKING FOUNTAINS AS PER IBC 2006, SECTION 1109.5 AND ANSI 117.1 SECTION 602.4
3. PROVIDE STRUCTUREAL CALCULATIONS AND DETAILS FOR MOUNTING OF ALL MECHANICAL ROOF MOUNTED EQUIPMENT AND FOR HOT WATER HEATER
4. IDENTIFY ACCESSIBLE ROUTE FROM HANDICAP PARKING TO ENTRANCE OF NEW FACILITYN AND STREET ACCESSIBLE ROUTES. SHOW ALL REQUIRED GRADE ELEVATIONS ALONG ENTIRE ROUTE TO REVIEW SLOPE COMPLIANCE
5. PLEASE NOTE INTENDED COMPLIANCE WITH IBC 2006, SECTION 1210.2, "...SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4' A.F.F.".
02/07/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/14/2008 GERRY KOZIOL WWM REVIEW Approved
02/25/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Justify the lack of heating for the restrooms. Reference Section 309, IMC 2006.
02/25/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Approved
02/25/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show that the water piping is protected from freezing.
2. Clarify how the 3-compartment sink is to be used. If the compartments are to be for washing, rinsing, and sanitizing, only the sanitizing compartment shall be indirectly wasted. If all three compartments are to used for holding ice and food for human consumoption, all three compartments shall have independent indirect wastes (if that is the case, then why is there a grease interceptor).
3. The water calculations refer to a flush tank system but the drawings and schedules refer to flush valves. Clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2008 VFLORES1 OUT TO CUSTOMER Completed