Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM00130
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/30/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
01/30/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PLEASE PROVIDE APPROVED BUILDING OFFICAL APPEAL FOR 3/32" FONT 2. CLARIFY HEIGHT OF DRINKING FOUNTAINS AS PER IBC 2006, SECTION 1109.5 AND ANSI 117.1 SECTION 602.4 3. PROVIDE STRUCTUREAL CALCULATIONS AND DETAILS FOR MOUNTING OF ALL MECHANICAL ROOF MOUNTED EQUIPMENT AND FOR HOT WATER HEATER 4. IDENTIFY ACCESSIBLE ROUTE FROM HANDICAP PARKING TO ENTRANCE OF NEW FACILITY. SHOW ALL REQUIRED GRADE ELEVATIONS ALONG ENTIRE ROUTE TO REVIEW SLOPE COMPLIANCE 5. PLEASE NOTE INTENDED COMPLIANCE WITH IBC 2006, SECTION 1210.2, "...SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4' A.F.F.". |
02/06/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/14/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/25/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Justify the lack of heating for the restrooms. Reference Section 309, IMC 2006. 2. Clarify the number of electric heaters to be installed. |
02/25/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
02/25/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the water piping is protected from freezing. 2. Clarify how the 3-compartment sink is to be used. If the compartments are to be for washing, rinsing, and sanitizing, only the sanitizing compartment shall be indirectly wasted. If all three compartments are to used for holding ice and food for human consumoption, all three compartments shall have independent indirect wastes (if that is the case, then why is there a grease interceptor). 3. Coordinate the plumbing floor plan with the riser diagram, i.e. provide water to the mop sink. 4. The water calculations refer to a flush tank system but the drawings and schedules refer to flush valves. Clarify. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/25/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |