Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved PLAN CHECK COMMENTS - PROJECT #T08CM00125

8/13/08 19 W. 17th STREET

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.


ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.


TRUSS REVIEW:
1. THE DESIGN SHOULD HAVE BEEN BASED ON THE 2006 IBC vs 2003 IBC.

2. SPECIFY THE JOIST HANGERS, NAIL PATTERNS, ETC. FOR THE TRUSS/TRUSS CONNECTIONS.

3. T-7, T-19, T-25 REQUIRE CONNECTIONS DESIGNED BY THE PROJECT ENGINEER.

4. ASK THE PROJECT ENGINEER TO REVIEW THESE TRUSSES FOR HER APPROVAL.