Permit Number: T08CM00123
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM00123
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2008 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/16/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. VERIFY CODE ANALYSIS AND STRUCTURAL CALCULATIONS MEET 2006 IBC REQUIREMENTS. BOTH LISTED AS 2003.
2. SHEET 4: DETAIL 1 AT SAMPLE FAUCET: HEIGHT OF SITE ENCLOSURE/WALL? NO PERMIT REQUIRED IF FENCE IS NOT OVER 6 FEET ABOVE FINISH GRADE.
3. SHEET 6: SECTION C AT BUILDING SECTION: KEY NOTE 7 SHOULD STATE LENGTH OF BEARING OF LINTEL ON BLOCK WALL.
4. SHEET 6: SECTION C AT BUILDING SECTION: KEY NOTE 12 SHOULD CLARIFY IF THERE SHOULD BE 2-#4 BARS TOP AND BOTTOM. NOTE STATES TWO, BUT SECTION ONLY INDICATES ONE BAR IN TOP.
5. SHEET 12: DETAIL 1 AT RADIO ANTENNA INSTALLATION: IS THE ANTENNA A 'TUCSON WATER PROPRIETARY DESIGN' ? IF NOT, FOOTING CALCULATIONS REQUIRED.
01/24/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/28/2008 ROBERT SHERRY WATER REVIEW Passed
01/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/28/2008 RSHERRY1 WWM REVIEW Passed No wastewater fixtures
01/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2008 CPIERCE1 OUT TO CUSTOMER Completed
03/06/2008 SHANAE POWELL REJECT SHELF Completed