Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM00122
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2008 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/16/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. VERIFY CODE ANALYSIS AND STRUCTURAL CALCULATIONS MEET 2006 IBC REQUIREMENTS. BOTH LISTED AS 2003. 2. SHEET 4: DETAIL 1 AT SAMPLE FAUCET: HEIGHT OF SITE ENCLOSURE/WALL? NO PERMIT REQUIRED IF FENCE IS NOT OVER 6 FEET ABOVE FINISH GRADE. 3. SHEET 6: SECTION C AT BUILDING SECTION: KEY NOTE 7 SHOULD STATE LENGTH OF BEARING OF LINTEL ON BLOCK WALL. 4. SHEET 6: SECTION C AT BUILDING SECTION: KEY NOTE 12 SHOULD CLARIFY IF THERE SHOULD BE 2-#4 BARS TOP AND BOTTOM. NOTE STATES TWO, BUT SECTION ONLY INDICATES ONE BAR. 5. SHEET 12: DETAIL 1 AT RADIO ANTENNA INSTALLATION: IS THE ANTENNA A 'TUCSON WATER PROPRIETARY DESIGN' ? IF NOT, FOOTING CALCULATIONS REQUIRED. |
| 01/24/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/28/2008 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 01/28/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/28/2008 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater fixtures |
| 01/28/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/06/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |