Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM00107
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2008 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM00107 2/13/08 9912 E. MANASSAS PLACE PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. LABEL ALL ROOMS AND SPACES. 2. PLEASE PROVIDE A LEGEND TO CLARIFY THE MEANING OF THE TERMS USED IN THE "OPERATING" COLUMN IN THE WINDOW SCHEDULE. ( NN, U, N, LNR, ETC. ) 3. THE INTERIOR ROOM BETWEEN THE ADDITION AND THE KITCHEN REQUIRES FRESH AIR BY WAY OF A WINDOW OR A FRESH AIR KIT ON THE MECHANICAL SYSTEM. IRC R301.1 EXC.1 , EICC 202, SUN ROOM . STRUCTURAL PLANS: 1. THE 2X6 RAFTERS APPEAR TO BE OVER SPANNED AT THE OVER FRAME OF THE EXISTING ROOF. 2. WHAT IS "HEEL HEIGHT? MENTIONED ON THE FRAMING PLAN. 3. PROVIDE A CROSS SECTION OF THE PORCH. 4. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES . TRUSS DATA MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS DATA SHEETS SHALL BE ROSSREFERENCED TO THE FLOOR PLANS. 5. PROVIDE THE EXISTING FRAMING THAT SUPPORTS ONE END OF THE PORCH RAFTERS. MEMBER SIZE AND SPAN. 6. PLEASE SPECIFY THE PORCH BEAM. 7. DESCRIBE THE EXISTING RAFTERS AND SPAN SUPPORTING THE GAS PACK. SECTIONS - DETAILS - MISC. NOTES: 1. PROVIDE A CROSS SECTION OF THE PORCH. 2. CROSS SECTION A-A / 6 ; THE BOTTOM OF THE FOOTING IS REQUIRED TO BE NOT LESS THAN 12" BELOW GRADE AND THE FLOOR NOT LESS THAN 6" ABOVE THE GRADE. THAT'S NOT LESS THAN 18" FLOOR TO BOTTOM OF FOOTING. PLEASE CORRECT. 3. MORE THAN ONE VAPOR BARRIER IS CONDUCIVE TO SWEATING. PLEASE CLARIFY THE VAPOR BARRIER(S) MENTIONED IN EXTERIOR WALL CONSTRUCTION / 6. PLUMBING PLANS: 1. NOTE WHICH PLUMBING CODE TO USE. 2. PLEASE CHECK THE SIZE OF THE GAS LINE BETWEEN THE FIREPLACE AND THE "T" TO THE GAS PACK. 3. THE WATER DISTRIBUTION SYSTEM APPEARS TO BE UNDER SIZED. 4. PLEASE CHECK THE FIXTURE UNIT COUNT PER FIXTURE USED IN THE SCHEDULE. MECHANICAL PLANS: 1. SEE FLOOR PLAN NOTE 3. ELECTRICAL PLANS: 1. PLEASE LOCATE LIGHT FIXTURES A, B, AND C AND PROVIDE CUT SHEETS FOT THEM. INCLUDE THE EXISTING EXTERIOR LIGHTS. ARE THE ALLOWABLE LUMENS PER ACRE CORRECT? 2. ELECTRICAL NOTE 3, THESE FIXTURES SHOULD BE LABELED AS SUITABLE FOR USE INWET AREAS. 3. PLEASE COMPLETE THE PANEL SCHEDULE. CIRCUIT AMPACITY AND WIRE GAGE MODEL ENERGY CODE: 1. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/14/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/14/2008 | SUE REEVES | REJECT SHELF | Completed |