Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00097
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/10/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/11/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the supports for the dessicant unit are connected to the structure. 2. If there is a ceiling located below the dessicant unit, show how maintenance access will be provided for the unit. |
| 01/11/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NEED STRUCTURAL CALCULATIONS FOR UNIT SUPPORT IN CEILING 2. CLARIFY CEILING ACCESS TO UNIT |
| 01/11/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/11/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/11/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 01/24/2008 | VFLORES1 | FIRE | REVIEW | Needs Review | |
| 01/24/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |