| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00091 7/8/08 1. See review results for 3/19/08. 2. Provide a lighting fixture schedule on the plans. 3. Indicate correct panel and circuit number for lights. C-18 is on the Site Plan, but Panel Schedules A and B are on the plans. Clarify. 4. Note location of panel/s on the plans. 5. Specify conduit size and type. 6. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 7. Provide a clear copy of lighting fixture cut sheets, with specific indication of fixtures intended for this project. 8. Provide load calculations for panels. 9. Specify depth of conduit fill. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/24/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |