Permit Number: T08CM00081
Parcel: 13011001E

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM00081
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2008 ROBERT SHERRY WATER REVIEW Denied A demand flow of 80 GPM through a 1-1/2" water meter results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits the 1-1/2" meter to a maximum demand of 50 GPM. Reference: Sections 610.2 and 610.12, UPC 2006.
04/16/2008 DAVE MANN FIRE REVIEW Denied Wholesale is not Group S-1, it is M. See IFC Section 202. Any interior walls will put the single path of travel over, 93 vs. 100. If the Group B part of building 2 is converted or used as retail the M area will be over 12000 sf and sprinklers will be required.
04/17/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/24/2008 TERRY STEVENS ZONING REVIEW Denied 04/24/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments: T08CM00081

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
04/24/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2008 DELMA ROBEY OUT TO CUSTOMER Completed
05/01/2008 SHANAE POWELL REJECT SHELF Completed