Permit Number: T08CM00080
Parcel: 136061570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00080
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2008 TERRY STEVENS ZONING REVIEW Approved
01/09/2008 PAUL MACHADO ENGINEERING REVIEW Approved
01/09/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00080 1/9/08

1. Please demonstrate compliance with the 2006 IECC due to the additional lighting.
2. Since Panel 2 is to have a MCB, and is series rated with the upstream remote main protective device, this could not be a 2-tiered system. Three tiered systems not available commercially. Sugggest to fully rate new Panel 2, or justify otherwise.
3. Minimum font size 1/8" for legibility. Please at least blow up the panel schedules to this standard.
01/09/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied NEED 1/8" LETTERING MINIMUM ON SEVERAL SHEETS.
NEED DEFERRED SUBMITTAL ON AUTOMATIC FIRE SPRINKLER SYSTEM.
BOTH OF THESE ITEMS NEED TO BE SUBMITTED TO JESSE SANDERS FOR A VARIANCE AND APPROVED BEFORE PLANS CAN BE APPROVED.
01/09/2008 MARTIN BROWN FIRE REVIEW Approved
01/16/2008 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
01/16/2008 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/16/2008 ROBERT SHERRY WATER REVIEW Approved
01/16/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/16/2008 CAGUILA1 WWM REVIEW Needs Review