Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00080
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
01/09/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
01/09/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00080 1/9/08 1. Please demonstrate compliance with the 2006 IECC due to the additional lighting. 2. Since Panel 2 is to have a MCB, and is series rated with the upstream remote main protective device, this could not be a 2-tiered system. Three tiered systems not available commercially. Sugggest to fully rate new Panel 2, or justify otherwise. 3. Minimum font size 1/8" for legibility. Please at least blow up the panel schedules to this standard. |
01/09/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | NEED 1/8" LETTERING MINIMUM ON SEVERAL SHEETS. NEED DEFERRED SUBMITTAL ON AUTOMATIC FIRE SPRINKLER SYSTEM. BOTH OF THESE ITEMS NEED TO BE SUBMITTED TO JESSE SANDERS FOR A VARIANCE AND APPROVED BEFORE PLANS CAN BE APPROVED. |
01/09/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/16/2008 | CAGUILA1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
01/16/2008 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
01/16/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/16/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
01/16/2008 | CAGUILA1 | WWM | REVIEW | Needs Review |