Permit Number: T08CM00078
Parcel: 133368580

Address:
158 N BONANZA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00078
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2/28/08 2nd review
Activity: T08CM00078
Address: 158 N. Bonaza
Applicant: Adrian Vildosola

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All plans should reference this code, or appeal to the Building Official for 2003-design approval.

FLOOR PLANS:
3. Specify the location of emergency rescue openings from existing bedrooms, R310 (max sill height 44", min. clear opening 24"H x 20"W @ 5 sq. ft net).

PLUMBING PLAN:
4. Fixture unit schedule required for the entire property (including existing) UPC Tables 6-5 and 7-3. The existing water supply system will be impacted by the installation of additional plumbing fixtures.
5. Specify the diameter of the water service line from the meter, UPC Table 6-6. The size of the water meter and the service line from the meter to the house must be reviewed for the additional plumbing fixtures. The Tucson Water policy adopted 3/2/07 limits the maximum demand for a 5/8" water meter (there are no ¾" meters for Tucson Water service) to 10GPM.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review