Permit Number: T08CM00047
Parcel: 116240450

Address:
52 N LAZY PL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM00047
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S-1: ADD GENERAL NOTE FOR 50 KSI STRUCTURAL STEEL PER CALCULATION PAGE 9.
2. SHEET S-3: INDICATE LLV ON LINTELS WITH
5X3 1/2X5/16 DOUBLE ANGLES.
3. SHEET S-8: SECTION 5: CALL OUT BEAM BEARING PLATE SIZE PER CALCULATION PAGE 11. VERIFY NO CONNECTION BETWEEN THE BEAM AND THE BEARING PLATE.
03/10/2008 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review